Burkert Type 8647 AirLINE SP is a modular electropneumatic valve island for integration into Siemens SIMATIC ET 200SP and ET 200SP HA. Features LC display and safety shut-off.

Burkert Type 8647 AirLINE SP is a modular, electropneumatic automation system consisting of connection and valve modules. It has been especially developed for safe and complete integration into the decentralised peripheral system "SIMATIC ET 200SP" and "SIMATIC ET 200SP HA" from Siemens. Pneumatically operated process valves, pneumatic cylinders or other pneumatic components can be connected to the pneumatic outputs. If the pneumatic components are installed with position feedbacks, the position of the actuated pneumatic components can be displayed on the associated pilot valve. This can save time on start-up and maintenance.

| Product properties | Type 0460, Type 6524, Type 6525 |
|---|---|
| Material | |
| Body | PA (polyamide), PC (polycarbonate) (valves: PA (polyamide), PPS (polyphenylene sulfide) or aluminum) |
| Seal | NBR (valves: FPM, NBR and PUR) |
| Width per station | 11 mm |
| Manual override | Standard |
| Number of valve slots | For single valves: max. 64 For impulse and double valves: max. 32 |
| Maximum number of valve functions | 64 on one valve block, several valve blocks possible on one station |
| Pneumatic Intermediate feed | Necessary after 24 valve functions For 2 × 3/2-way valve: necessary after 16 valve functions |
| Performance data | |
| Pressure data | Overpressure to atmospheric pressure |
| Pressure range | Vac...10 bar (with UL approval Vac...8 bar) |
| External supply air (auxiliary pilot air) | >2.5 bar (Type 0460: not possible) |
| Flow rate QNn value air | 200...300 l/min measured at + 20 °C, 6 bar pressure at valve inlet and 1 bar differential pressure |
| Flow rate QNn value air with integrated P shut-off | Flow reduced by approx. 20 % |
| Nominal operating mode | Continuous operation (100 % duty cycle) |
| Electrical data | |
| Operating voltage | 24 V DC |
| Voltage tolerance | ±10 % |
| Residual ripple (at DC) | 2.4 Vss |
| Nominal power of each valve | For single valves: 0.8 W For impulse and double valves: 2× 0.8 W with power reduction |
| Nominal current of each valve | 40 mA (28 mA holding current after 120 ms), 20 mA (when using Type 0460) |
| Protection class | III according to DIN EN 61140, VDE 0140 |
| Safety-related shut-off | Shut-off of individual valve via second connection Module-based shut-off (EVS function) Block-based shut-off (valve island) via Siemens F-PMe module |
| Medium data | |
| Operating medium | Oil-free or lubricated compressed dry air (5 μm filter recommended) |
| Compressed air quality | ISO 8573 - 1: 2010, Class 7.4.4 |
| Approvals and conformities | |
| Degree of protection | IP20, IP65 in closed control cabinets |
| Product connections | |
| Working port | D 6, D 1/4, ALQ |
| Air supply connection | G 1/4, D 3/8 |
| Communication module | Siemens SIMATIC ET 200SP / SP HA |
| Communication interface | PROFIBUS DP, PROFINET IO |
| Environment and installation | |
| Installation position | As required, preferably with actuator upright |
| Storage temperature | - 20 °C...+ 60 °C |
| Ambient temperature | 0 °C...+ 55 °C (for valve Type 0460: 0 °C...+ 50 °C) |
Note
The maximum flow rate depends on the valve function. With ET 200SP HA, only one valve block is possible.

| Pilot valve Type | Type 6524, Type 6525 | Type 6524 |
|---|---|---|
| Circuit function | 3/2 and 5/2-way valve | 2 × 3/2-way valve |
| Material | ||
| Body | PA (polyamide) | |
| Seal | FKM, NBR and PUR | |
| Width per station | 11 mm | |
| Manual override | Standard | |
| Pneumatic module | With plug-in coupling, ∅ 6 mm, ∅ 1/4" | |
| Performance data | ||
| Flow rate QNn value air | 300 l/min | 300 l/min |
| Duty cycle | Continuous operation (100 % duty cycle) | Continuous operation (100 % duty cycle) |
| Electrical data | ||
| Operating voltage | 24 V DC (10 % residual ripple permissible) | 24 V DC (10 % residual ripple permissible) |
| Nominal power of each valve | 0.8 W | 2 × 0.8 W with reduction of power |
| Product connections | ||
| Service port 2 (A), 4 (B) | Plug-in coupling ∅ 6 mm, ∅ 1/4" | |
| Air supply connection 1 (P), 3 (R), 5 (S) | G 1/4 |

| Pilot valve Type | Type 0460 |
|---|---|
| Circuit function | 5/2-way and 5/3-way bistable |
| Material | |
| Body | Aluminium |
| Seal | NBR |
| Width per station | 11 mm |
| Manual override | Standard |
| Pneumatic module | With plug-in coupling, ∅ 6 mm, ∅ 1/4" |
| Performance data | |
| Flow rate QNm value air | 200 l/min |
| Electrical data | |
| Operating voltage | 24 V DC ± 10 % |
AirLINE Quick considerably reduces the use of components in the control cabinet. With the AirLINE Quick Adapter, the valve terminal is adapted directly to the control cabinet floor or control cabinet wall.

Advantages:
Note
The valves of Type 0460 valves cannot be installed with AirLINE Quick due to their size.
| Description | Circuit function |
|---|---|
| Circuit function C (CF C) 3/2-way solenoid valve Servo-controlled, with manual override Normally closed | C (CF C) |
| Circuit function C (CF C) 2 × 3/2-way solenoid valve Servo-controlled, with manual override Normally closed | C (CF C) |
| Circuit function D (CF D) 3/2-way solenoid valve Servo-controlled, with manual override Normally open | D (CF D) |
| Circuit function H (CF H) 5/2-way solenoid valve Servo-controlled, with manual override Pressure applied via port (1), therefore one of the two ports (2) or (4) is under pressure. | H (CF H) |
| Circuit function L (CF L) 5/3-way solenoid valve With manual override In middle position all ports locked | L (CF L) |
| Circuit function N (CF N) 5/3-way solenoid valve With manual override In middle position ports 2 and 4 exhausted | N (CF N) |
| Circuit function Z (CF Z) 5/2-way solenoid valve Impulse variant with 2 coils and manual override Pressure applied via port (1), therefore one of the two ports (2) or (4) is under pressure. | Z (CF Z) |
| Description | Circuit function |
|---|---|
| Circuit function C (CF C) 3/2-way solenoid valve Servo-controlled Normally closed | C (CF C) |
| Circuit function C (CF C) 2 × 3/2-way solenoid valve Servo-controlled Normally closed | C (CF C) |
| Circuit function D (CF D) 3/2-way solenoid valve Servo-controlled Normally open | D (CF D) |
| Circuit function G (CF G) 4/2-way solenoid valve Servo-controlled | G (CF G) |
| Approval | Description |
|---|---|
| Explosion protection | Optional: Explosion protection. As a category 3 device suitable for zone 2. ATEX: BVS 18 ATEX E 078 X II 3G Ex ec IIC T4 Gc IECEx: IEC Ex BVS 18.0068 X Ex ec IIC T4 Gc |
| UL Listed | Optional: UL Listed for the USA and Canada. The products are UL Listed for the USA and Canada according to: UL 61010-1 CAN/CSA-C22.2 No. 61010-1 |
Explore similar products in our catalog