High Flow RatesIP65/67NEMA Type 4XATEX/IECEx

BURKERT 20091739 2100 Pneumatically Operated 2/2-Way Angle Seat Valve ELEMENT

Burkert Type 2100 pneumatically operated 2/2-way angle seat valve ELEMENT for decentralized automation. Features high flow rates, long service life, and stainless steel body.

BURKERT 20091739 2100 Pneumatically Operated 2/2-Way Angle Seat Valve ELEMENT

Burkert Type 2100 pneumatically operated 2/2-way angle seat valve ELEMENT is specially optimised for decentralized process automation and fulfils the tough criteria in process environments. Its unique design allows easy integration of automation units in all expansion stages, from electrical/optical position feedback to pneumatic control and integrated fieldbus interface. Maximum service life and tightness are achieved by the proven self-adjusting v-seal packing gland. The highly integrated system of valve and automation unit is characterised by its compact and smooth design, integrated pilot air ducts, protection classes IP65/67, NEMA Type 4X and high resistance to chemicals.

BURKERT 20091739 Burkert 2100 pneumatically operated 2/2-way angle seat valve ELEMENT

Features

  • High flow rates
  • Long service life
  • Easy integration of automation units with ELEMENT
  • Flow-optimised stainless steel valve body with sleeve, clamp or weld connection
  • Suitable for steam

General Technical Data

Product properties
DesignAngle seat valve
Nominal diameter (port connection)DN 10...DN 80, NPS 3/8...NPS 3
Safety setting in case of power failureNormally closed (control function A), normally open (control function B)
Flow directionFlow to open (below seat), flow to close (above seat)
Operating pressure0 bar(g)...25 bar(g), vacuum variants...- 0.9 bar(g) (option)
Nominal pressurePN 25 (DIN EN 1333), Class 150 (DIN EN 1759)
Pilot pressure2.5 bar(g)...10 bar(g)
Seat leakageLeakage rate A (DIN EN 12266 - 1), seat seal PTFE and PEEK, test medium air
Operating mediumSteam, water, neutral gases, alcohols, oils, fuels, hydraulic fluids, salt solutions, alkalis, organic solvents, oxygen and fuel gases
Medium temperature- 40 °C...+ 230 °C
ViscosityMax. 600 mm²/s
Control mediumAir, neutral gases
Ambient temperature- 10 °C...+ 100 °C
Degree of protectionIP65/67
Installation positionAs required, preferably with actuator in upright position

Control Functions

WARNING

Risk of damage due to bursting pipes and bursting equipment when the flow is above the seat. In the case of liquid mediums, water hammer can occur causing pipes and the device to burst. Do not use valves with flow above the seat for liquid mediums.

Flow direction below seat for liquids, steam and gases

  • Control function A (CF A): Pneumatically operated 2/2-way on/off valve. Flow direction below seat. Normally closed by spring force.
  • Control function B (CF B): Pneumatically operated 2/2-way on/off valve. Flow direction below seat. Normally opened by spring force.

Flow direction above seat for steam and gases

  • Control function A (CF A): Pneumatically operated 2/2-way on/off valve. Flow direction above seat. Normally closed by spring force.

Approvals and Conformities

  • Explosion protection: EPS 18 ATEX 2 008 X II 2G Ex h IIC T4…T2 Gb / II 2D Ex h IIIC T135 °C…T300 °C Db. IECEx EPS 18.0007X.
  • Drinking water: Suitable for use in drinking water applications. The materials comply with the assessment principles (UBA).
  • Foods and beverages/Hygiene: FDA (Code of Federal Regulations), USP (United States Pharmacopeial Convention), EC Regulation 1935/2004, China food GB Standards.
  • DNV GL classification: Accepted for installation on all vessels classed by DNV GL.
  • Oxygen: Optional suitability for gaseous oxygen.
  • Fuel gases: Complies with Regulation (EU) 2016/426 and DVGW DIN EN 161.

Materials

BURKERT 20091739 Burkert 2100 material specifications and components

No.ElementMaterial
1Ground terminalStainless steel 1.4301/1.4305 only for ATEX variant
2Optical position indicatorPolysulfone PSU
3Pilot air portsPush-in connector PP (Standard). On request: Thread G 1/8" Stainless steel 1.4305
4Actuator coverPPS
5Actuator casingStainless steel 1.4561 (316Ti)
6Piston sealFKM
7SpringStainless steel 1.4310
8PipeStainless steel 1.4401 (316)/1.4404 (316L)
9Packing glandPTFE V-Rings (filled), with spring compensation
10SpindleStainless steel 1.4401 (316)/1.4404 (316L)
11Spindle guidePEEK
12Body sealGraphite, PTFE (Option)
13Swivel plateStainless steel 1.4401 (316)/1.4404 (316L)
14Seat sealPTFE, PEEK (Option)
15Valve bodyStainless steel CF3M

INFO

The lubricants for packing gland and actuator are classified according to NSF H1.

Dimensions

Actuator

BURKERT 20091739 Burkert 2100 actuator dimensions

Nominal diameter DNNPSActuator size ∅∅ A [mm]B [mm]H [mm]K/M [mm]
151/250 (D)64.5166163147
151/270 (M)91182178156
203/450 (D)64.5174171155
203/470 (M)91189186163
25150 (D)64.5175173156
25170 (M)91191188165
25190 (N)120229228203
321 1/470 (M)91201197174
321 1/490 (N)120243242217
401 1/270 (M)91204201178
401 1/290 (N)120246245220
50270 (M)91223219196
50290 (N)120262261236
502130 (P)159312312273

Body with threaded connection

BURKERT 20091739 Burkert 2100 body with threaded connection dimensions

DNNPSGNPTRCCMLMAF
151/21413.713.2246527
203/41614.014.5277534
2511816.816.829.59041
321 1/41617.319.13611050
401 1/21817.319.13512055
5022417.623.44515070

Principle of Operation

Flow direction below the seat

Only use flow direction below the seat for liquid media, gases, and vapours. As the medium is present under the swivel plate, the operating pressure contributes to the opening of the valve.

BURKERT 20091739 Burkert 2100 flow direction below seat

Flow direction above the seat

Only use flow direction above the seat for gases and vapours, and valves with control function A (closed by spring force in rest position). As the medium is present above the swivel plate, the operating pressure contributes to the closing of the valve. The operating pressure also supports the sealing of the valve seat.

BURKERT 20091739 Burkert 2100 flow direction above seat

Safety Instructions

DANGER

Medium under pressure Medium under pressure can seriously injure people. In the event of overpressure or pressure surges, the device or lines can burst. Pneumatic lines that are defective or not securely fastened can come loose and swing around.

  • Before working on the device or system, switch off the pressure. Vent or empty the lines.
  • Adhere to the permitted pressure ranges of the medium.

WARNING

Contaminated pilot air The control exhaust air of the device can be contaminated with lubricants and damage the health of people and the environment. Dissipate control exhaust air appropriately.

TIP

Installation position Any installation position is permitted, but preferably with the actuator facing up. Ensure correct position and integrity of the seal in the body connection. Grease the thread of the body connection before installation.