Skip to content
AirLINE QuickHot SwapATEX/IECEx Zone 2PROFIBUS DPV1

BURKERT 338636 Type 8652 Valve Island, 16-Bank ALQ VA

BURKERT 338636 Type 8652 16-bank valve island optimised for process automation. Features AirLINE Quick, Hot Swap, PROFIBUS DPV1, and ATEX/IECEx Zone 2 approvals.

BURKERT 338636 Type 8652 Valve Island, 16-Bank ALQ VA

BURKERT 338636 Type 8652 is a 16-bank valve island especially developed for process automation requirements. New diagnostic functions can be visualised on the LC display, both in clear text as well as symbols. This makes it easy to relate to the shown messages and helps to save time during start-up and maintenance. Furthermore, the diagnostic message is also available at the controller, enabling a fast overview of the plant status. The hardware is optimised for installation at the bottom of the control cabinet. Moreover, key pneumatic functions ensure increased process reliability, such as check valves in the exhaust air ducts that prevent unplanned actuation due to pressure peaks.

General Technical Data

FeatureDescription
Body MaterialPA (polyamide)
Seal MaterialNBR and PUR
Width per station11 mm
Pressure rangeVac...10 bar
External supply air3...10 bar
Operating voltage24 V DC (±10% tolerance)
Protection classIII according to DIN EN 61140, VDE 0140
Degree of protectionIP20, IP65 in closed control cabinets
Ambient temperature-10 °C...+55 °C

AirLINE Quick

AirLINE Quick considerably reduces the use of components in the control cabinet. With the AirLINE Quick Adapter, the valve terminal is adapted directly to the control cabinet floor or wall.

Advantages:

  • Reduced space requirement in the control cabinet
  • Enables the use of more compact control cabinets
  • Reduced installation effort due to hose connections directly at the bottom

BURKERT 338636 Type 8652 AirLINE Quick Adapter

Approvals and Conformities

  • Explosion protection: ATEX (BVS 20 ATEX E 031 U), IECEx (IECEx BVS 20.0024 U)
  • North America: UL Listed, UL Recognized for Hazardous Locations
  • Others: China Compulsory Certification (CCC)

Dimensions

Variant 16-, 20- and 24-fold

Note

Dimensions in mm, unless otherwise stated.

BURKERT 338636 Type 8652 Dimensions 16 to 24 fold

VariantABCDmm'n
16-fold with intermediate supply11222410 x M5114.3774
20-fold with intermediate supply13426810 x M5158.31175
24-fold with intermediate supply15631210 x M5158.311116
16-fold without intermediate supply9919810 x M5-15-4
20-fold without intermediate supply12124210 x M5-19-5
24-fold without intermediate supply14328610 x M5-23-6

Product Connections

Power Supply for Communication and Displays

Connect the 5-pin spring-loaded terminal according to the pin assignment. Possible cable cross-section: ≤ 1.5 mm².

PinColourAssignment
1Red24 V DC
2WhiteCAN_H (büS connection)
3GreenSHIELDING
4BlueCAN_L (büS connection)
5BlackGND

Power Supply for Pneumatic Valves

The interface plate has a 2-pin spring-loaded terminal to which the pneumatic valves’ power supply is connected.

ClipColourAssignment
1RedAUX 24 V
2BlackGND

Product Installation

Installation Situation Inside the Control Cabinet

To use the Hot Swap function, always observe a minimum distance to the front edge of the control cabinet when installing the valve island inside the control cabinet.

BURKERT 338636 Type 8652 Installation situation inside control cabinet

Product Design and Assembly

Electronic Module with Digital Inputs (Optional)

The digital inputs are supplied (24 V) by the electronic module. Current is limited to maximum 30 mA per digital input. Standard 3-wire sensors and 2-wire sensors with voltages between 10…30 V as well as mechanical limit switches can be used.

Type 6534 valves are equipped with additional connection terminals. A valve circuit can therefore be interrupted by an external switch. Manual override is not required for these valve variants. To use the shut-off function, connect the terminal to a potential-free contact (mechanical switch or relay).