Bürkert 20074754 Type 7011 direct-acting 2/2-way plunger valve. Features a brass body, M5 internal thread, 1.2mm orifice, FKM seal, and 24V DC operation for 0-16 bar pressure ranges.

Bürkert 20074754 Type 7011 is a direct-acting and compact small plunger valve up to DN 2.4. To increase pressure resistance and leak-tightness, the stopper and the core guide tube are welded together. This specific model features a brass body, FKM seals, an M5 internal thread connection, and operates on 24 V DC. It is designed for circuit function A (normally closed) and is suitable for neutral gaseous and liquid media.
The valve utilizes a slipped-over coil system and allows for simple and fast mounting. In combination with a suitable plug conforming to DIN EN 175301-803 shape B, the valve satisfies the IP65 degree of protection.
| Feature | Specification |
|---|---|
| Orifice | DN 1.2 |
| Body material | Brass |
| Seal material | FKM (Fluor rubber) |
| Operating voltage | 24 V DC |
| Nominal pressure | 0 to 16 bar |
| Medium temperature | -10 °C to +100 °C |
| Ambient temperature | -10 °C to +75 °C |
| Viscosity | Max. 21 mm²/s |
| Degree of protection | IP65 (with suitable connector) |
Circuit function A (CF A): 2/2-way solenoid valve, direct-acting, normally closed.

| No. | Element | Material |
|---|---|---|
| 1 | Nut | DIN 176 Surface finish thick film passivated KOSA0101 |
| 2 | Stopper | Stainless steel 1.4113/434 |
| 3 | Core guide tube | Stainless steel 1.4303 ST/305L |
| 4 | Shading ring | Copper (optional silver) |
| 5 | Core | Stainless steel 1.4113/434 |
| 6 | Spring | Stainless steel 1.4310/301 |
| 7 | Seal | FKM |
| 8 | Valve body | Brass |
| 9 | O-ring | FKM |
| 11 | Coil | Epoxy |
Threaded Variant

| Port connection | A [mm] | B [mm] | C [mm] | D [mm] |
|---|---|---|---|---|
| M5 | 5 | 20 | 10 | 10 |
Safety Instructions
Risk of injury from high pressure in the system or device Before working on the system or device, switch off the pressure and ventilate and empty the lines.
Risk of injury from electric shock Before working on the system or device, switch off the power supply and secure against reactivation. Observe the applicable accident prevention and safety regulations for electrical devices.