BURKERT 20079412 8652 AirLINE Valve Island for Process Automation

Burkert Type 8652 AirLINE valve island optimised for process automation. Features LC display diagnostics, safety-related shut-off, and EX-variants for Zone 2.

BURKERT 20079412 8652 AirLINE Valve Island for Process Automation

Burkert Type 8652 AirLINE is a valve island especially developed for process automation requirements. New diagnostic functions can be visualised on the LC display, both in clear text as well as symbols. This makes it easy to relate to the shown messages and helps to save time during start-up and maintenance. Furthermore, the diagnostic message is also available at the controller, enabling a fast overview of the plant status. The hardware is optimised for installation at the bottom of the control cabinet, though installation on a standard rail is also possible. Key pneumatic functions ensure increased process reliability; for instance, check valves in the exhaust air ducts make sure there is no unplanned actuation due to pressure peaks.

BURKERT 20079412 Burkert Type 8652 installation situation inside the control cabinet

General Technical Data

Product propertiesDescription
Body MaterialPA (polyamide)
Seal MaterialNBR and PUR
Width per station11 mm
Number of valve slotsMax. 24
Maximum valve functionsMax. 48
Manual overrideLatching, spring return (optional: lockable)
Pneumatic intermediate supplyOptional for the variants with 16, 20 and 24 valve slots
Performance dataDescription
Pressure rangeVac...10 bar
External supply air3...10 bar
Flow rate $Q_{Nn}$ value air310 l/min (measured at +20 °C, 6 bar pressure at valve inlet and 1 bar differential pressure)
Flow rate with Hot SwapFlow reduced by approx. 3%
Nominal operating modeContinuous operation (100 % duty cycle)
Electrical dataDescription
Operating voltage24 V DC (±10% tolerance)
Nominal power per valve0.7 W (0.175 W after power reduction)
Nominal current per valve29 mA (10 mA after power reduction)
Digital inputMax. 48
Environment and installationDescription
Ambient temperature-10 °C...+55 °C
Storage temperature-20 °C...+60 °C
Degree of protectionIP20, IP65 in closed control cabinets

AirLINE Quick

AirLINE Quick considerably reduces the use of components in the control cabinet. With the AirLINE Quick Adapter, the valve terminal is adapted directly to the control cabinet floor or control cabinet wall.

Advantages:

  • Reduced space requirement in the control cabinet
  • This makes it possible to use more compact control cabinets
  • Reduced installation effort due to hose connections directly at the bottom of the control cabinet

BURKERT 20079412 Burkert Type 8652 AirLINE Quick Adapter in stainless steel or anodised aluminium

Circuit Functions

Standard Functions

Circuit functionDescription
C (CF C)3/2-way solenoid valve, servo-controlled, with manual override, normally closed
C (CF C)2 × 3/2-way solenoid valve, servo-controlled, with manual override, normally closed
D (CF D)2 × 3/2-way solenoid valve, servo-controlled, with manual override, normally open
H (CF H)5/2-way solenoid valve, servo-controlled, with manual override. Pressure applied via port (1), therefore one of the two ports (2) or (4) is under pressure.
L (CF L)5/3-way solenoid valve, with manual override. In middle position all ports locked
M (CF M)5/3-way solenoid valve, servo-controlled, with manual override. In middle position ports 2 and 4 ventilated
N (CF N)5/3-way solenoid valve, with manual override. In middle position ports 2 and 4 exhausted
Z (CF Z)5/2-way solenoid valve, impulse variant with 2 coils and manual override. Pressure applied via port (1).
Circuit functionDescription
C (CF C)3/2-way solenoid valve, servo-controlled, normally closed
C (CF C)2 × 3/2-way solenoid valve, servo-controlled, normally closed
H (CF H)5/2-way solenoid valve, servo-controlled. Pressure applied via port (1).
L (CF L)5/3-way solenoid valve, servo-controlled. In middle position all ports locked

Approvals and Conformities

  • Explosion protection (Optional): As a category 3 device suitable for zone 2/22. ATEX: II 3G Ex ec IIC Gc / II 3D Ex tc IIIC Dc. IECEx: Ex ec IIC Gc / Ex tc IIIC Dc.
  • North America (Optional): UL Listed for the USA and Canada (UL 61010-1). UL Recognized for Hazardous Locations (Class I, Zone 2; Class II, Zone 22; Class I, Division 2).
  • CCC (Optional): China Compulsory Certification for hazardous applications in China.

Dimensions

Variant 4-, 8- and 12-fold

BURKERT 20079412 Burkert Type 8652 dimensions for 4-, 8- and 12-fold variants

Variant 16-, 20- and 24-fold

BURKERT 20079412 Burkert Type 8652 dimensions for 16-, 20- and 24-fold variants

Product Connections

Power supply for communication and displays

Connect the 5-pin spring-loaded terminal according to the pin assignment (Possible cable cross-section: ≤ 1.5 mm²).

PinColourAssignment
1Red24 V DC
2WhiteCAN_H (büS connection)
3GreenSHIELDING
4BlueCAN_L (büS connection)
5BlackGND

Power supply for pneumatic valves

The interface plate has a 2-pin spring-loaded terminal to which the pneumatic valves’ power supply is connected.

ClipColourAssignment
1RedAUX 24 V
2BlackGND

Product Design and Assembly

BURKERT 20079412 Burkert Type 8652 interface plate 24V without modular shut-off

Electronic module with digital inputs (optional)

The digital inputs are supplied (24 V) by the electronic module. Current is limited to maximum 30 mA per digital input. Standard 3-wire sensors and 2-wire sensors with voltages between 10…30 V as well as mechanical limit switches can be used.

Type 6534 valves are equipped with additional connection terminals. A valve circuit can therefore be interrupted by an external switch. Manual override is not required for these valve variants. To use the shut-off function, connect the terminal to a potential-free contact (mechanical switch or relay).

Example configuration

BURKERT 20079412 Burkert Type 8652 example network configuration

Safety Instructions for Hazardous Locations

Voltage Hazards

  • Before working on the device or system, switch off the power supply. Secure against reactivation.
  • In an existing explosive atmosphere, the connection terminals for 24 V supply, SIA, EVS, and digital inputs may only be plugged in or unplugged when the power is switched off.
  • The Hot Swap function is prohibited in an existing explosive atmosphere.

Electrostatic Charge

  • Take appropriate measures to ensure that no electrostatic charge can build up in the potentially explosive area.
  • Only clean the device surface by wiping it gently with a damp or antistatic cloth.

Special Conditions for Safe Use

  • For explosion protection type "ec", install the device in an enclosure that complies with the applicable requirements of EN/IEC 60079-0 and EN/IEC 60079-7, with a degree of protection of at least IP54.
  • For explosion protection type "tc" (dust), install the device in an enclosure that complies with EN/IEC 60079-0 and EN/IEC 60079-31, with a degree of protection of at least IP6X.
  • Only use the device in an area with a pollution degree of at least 2 as defined in IEC 60664-1.