BURKERT Type 8640 modular valve island (SKU 20088850). Features 33mm add-on dimension, G 1/2 pressure port, 2-8 bar pressure range, and DIN-rail mounting.

BURKERT Type 8640 modular valve island system is designed to solve diverse and complex control problems due to its systematic modular construction and combination of pneumatic and electrical interfaces. By putting together a row of pneumatic modules with different numbers of valves, 2 to 24 valve functionalities may be realized on one valve unit. Electrical connectivity is achieved by either fieldbus interfaces, common connection (parallel connection technique) or multipin interfaces. The valves allow different applications to be covered. Bodies and connection modules are made of high-quality plastic (polyamide) and are easy to assemble by means of the built-in snap connectors.

Key advantages of the Type 8640 system include its compact design, modular configuration, and higher flexibility in the control cabinet due to AirLINE Quick compatibility. It allows for the simple exchange of valves, which is also possible during operation when equipped with the "P-shut-off" option.
The Type 8640 valve island can be equipped with various pilot valves (such as Type 0460, 6524, 6525, 6526, 6527, and 5470) to suit different application requirements.
| Product Properties | Type 0460, 6524, 6525 | Type 6526, 6527 | Type 5470 |
|---|---|---|---|
| Body Material | PA (polyamide), aluminium (Type 0460) | PA (polyamide), aluminium | PA (polyamide) |
| Seal Material | FKM, NBR and PUR | NBR | NBR |
| Width per station | 11 mm | 16.5 mm | 19 mm |
| Manual override | Standard | Standard | Standard |
| Number of valve slots | Max. 24 (Max. 12 for impulse/double valves) | Max. 24 | Max. 24 |
| Pressure range | Vac...10 bar | Vac...10 bar | Vac. 2...10 bar |
| Nominal operating mode | Continuous operation (100% duty cycle) | Continuous operation (100% duty cycle) | Continuous operation (100% duty cycle) |
| Operating voltage | 24 V DC (±10% tolerance) | 24 V DC (±10% tolerance) | 24 V DC (±10% tolerance) |
| Operating medium | Oil-free or lubricated compressed dry air, neutral gases (5 μm filter recommended) | Oil-free or lubricated compressed dry air, neutral gases (5 μm filter recommended) | Oil-free or lubricated compressed dry air, neutral gases (5 μm filter recommended) |
| Degree of protection | IP20 (IP65 in closed control cabinets) | IP20 (IP65 in closed control cabinets) | IP20 (IP65 in closed control cabinets) |

WARNING
Crushed O-rings and profile seals lead to leaky blocks. Fasten each valve to the base module with 2 screws. Recommended tightening torque is 0.6 ±0.1 Nm.

Standard rail installation:
Wall installation:
Observe the following tightening torques when screwing into the port connections. The specified tightening torque may vary depending on the sealing system.
| Port size | Marking/function | Recommended tightening torque [Nm] | Maximum tightening torque [Nm] |
|---|---|---|---|
| G1/4, NPT1/4 | P, R/S connection | 4...7 | 20 |
| G1/8, NPT1/8 | P, R/S connection A/B valve outlets | 3...6 | 7 |
| Fault | Possible cause | Remedy |
|---|---|---|
| Valves do not switch | No operating voltage or operating voltage too low | Check electrical connection. Ensure operating voltage according to type label. |
| Manual override not in zero position | Bring manual override to zero position. | |
| Pressure supply insufficient or not available | Set up large-volume pressure supply. Minimum operating pressure ≥ 2 bar. | |
| Valves switch with a delay or blow off at the exhaust ports | Pressure supply insufficient or not available | Set up large-volume pressure supply. Minimum operating pressure ≥ 2 bar. |
| Valves are not in the home position (de-energised) during pressure build-up | Apply pressure to the valve block before the valves are switched. | |
| Insufficient ventilation of the exhaust air ducts due to too small or dirty silencers | Use suitably sized silencers or expansion vessels. Clean the dirty silencers. | |
| Impurities or foreign matter in the pilot or pneumatic valve | Apply pulsed pressure to the exhaust air ducts to blow out the impurities. Install a new pilot or pneumatic valve. | |
| Leaky valve blocks | Missing or crushed O-rings between the modules | Identify leak or missing seals. |
| Missing or incorrectly positioned flat seals between valve and base plate | Insert missing seals or replace damaged seals. |